Products

Non Return Boiler Angle Valve, Fig 1408

Lunkenheimer Non Return Angle Valve, Outside screw and yoke

Fig 1408

Lunkenheimer non-return valves cut out a boiler automatically when inside pressure drops suddenly or when heat is withdrawn. External spring is reversed and valve acts as a spring-loaded stop-check valve.

Spring may be adjusted from the outside while valve is under pressure to compensate for excessive steam pulsations. Valves may be installed in either vertical or horizontal position.


Bodies and bonnets
Cast iron, ASTM A-126.

Trim
Seat, disc, back seat bushing and yoke bushing is S1 steam bronze. ASTM B-61.

Seating surfaces
Regrindable. Seat, disc and all other parts renewable.

Flanges
Dimensions, drilling, and facing conform to American Cast Iron Flange Standard. Class 250, (ANSI B16.2 1960). Raised face is ⅒”.

Installation note
Connection should be made directly to boiler outlet nozzle. Intervening pipe should be kept as short as possible. Normally shipped with external spring positioned for vertical installation. The external spring should be reversed when the valve is installed with the stem horizontal. Complete information for installation and operation is attached to valve when shipped.

Alternatives
Fig 1409 Cast Steel Class 300


Fig 1408

Lunkenheimer Quality

Download

Lunkenheimer-Angle-Valve-Cast-Iron-Fig1408

Pressure ratings:

250 lb SP

Body materials:

Cast iron

Temperature:

450°F

Sizes:

3" - 8"